Page 103 - CPVC Fire Sprinkler Products Installation Instructions & Technical Handbook
P. 103

IMPORTANT INFORMATION 101
IMPORTANT INFORMATION WITH REGARDS TO YOUR TYCO CPVC FIRE SPRINKLER SYSTEM
CONGRATULATIONS, your building structure contains a state-of-the-art life safety system. Your TYCO CPVC fire sprinkler system will enhance the safety and security of your building when properly maintained. TYCO CPVC Fire Sprinkler Products resist attack from a wide range of chemicals that are corrosive to metallic piping. As with any piping material, there are, however, certain chemicals that can be detrimental to CPVC. Occasionally some of these chemicals may be found in some construction products, site preparations and building maintenance. There are certain things that you need to be mindful of in caring for or working around your TYCO CPVC fire sprinkler system.
Keep your system clear from contact with the following products and chemicals unless product labels state materials are compatible with CPVC:
 NOTICE
Ordinary considerations
For hired contractors & do-it-yourselfers
Property maintenance services
    Cleaning Products Detergents, Oils/Lubricants/ Greases, Rubbery Materials
  Fungicides,
Mold Remediation Chemicals, Termiticides/Insecticides
   Corrosion Inhibitors, Glycol-based antifreezes, Solder Flux, Thread Sealants
Flexible Cable/Wiring
(especially communications cabling) Caulks/Mastics, Adhesive, Vinyl/Electrical Tape Non-Approved Spray Foam Insulation Non-Water Based Paint, Paint Thinners Wood Finishes / Varnishes
 You should also avoid the following:
• Sitting, standing, hanging, leaning, or resting anything on the pipe, fittings, and sprinklers
• Grounding electrical wiring to the pipe or fittings
• Ambienttemperaturesbelow40°F(4,4°C)whereyourfiresprinklersystemislocated. (Unless an approved compatible antifreeze or insulation method is installed.)
• Hot work around the pipe, for example, blow torches, soldering, etc.
Be certain that this document is reviewed and understood by anyone working on or around your CPVC life safety system. If you have any questions or need assistance on chemical compatibility with your TYCO CPVC fire sprinkler system, contact the manufacturer of the chemical or non-CPVC product in question.
Proper care will help your TYCO CPVC fire sprinkler system provide protection for years to come.
FOR ADDITIONAL INFORMATION VISIT
TYCO FIRE PROTECTION PRODUCTS AT WWW.TYCO-FIRE.COM
 8











































































   101   102   103   104   105